HZJD-2 Transformer Oil Tan Delta And Resistivity Tester
HZJD-2 Transformer Oil Tan Delta and Resistivity Tester Products Description I. Overview The Insulating Oil Dielectric Loss and Electrical Resistivity Tester complies with the Chinese National Standard GB/T5654-2007 ( Liquid insulating materials - Measurement of relative permittivity, dielectric...
HZJD-2 Transformer Oil Tan Delta and Resistivity Tester
Product Description
I. Overview
The HZJD-2 Insulating Oil Dielectric Loss and Electrical Resistivity Tester complies with the Chinese National Standard GB/T5654-2007 (Liquid insulating materials - Measurement of relative permittivity, dielectric dissipation factor and d.c. resistivity). It is primarily designed for measuring the dielectric loss factor (tan δ) and DC resistivity of liquid insulating media, such as transformer oil.
II. Key Features & Functions
Standardized Test Cell: Employs a GB/T5654-2007 compliant three-electrode structure (2mm gap) to minimize stray capacitance and leakage effects on tan δ measurements.
Precise Temperature Control: Uses medium-frequency induction heating with a PID algorithm for non-contact, uniform, rapid heating. Temperature is strictly maintained within the preset range (0–125°C).
Stable Reference Capacitor: Features an internal SF6 gas-filled three-electrode capacitor, ensuring tan δ and capacitance stability unaffected by ambient temperature/humidity, guaranteeing long-term accuracy.
Stable AC Power Supply: Employs AC-DC-AC conversion, eliminating the impact of mains voltage and frequency fluctuations on measurement accuracy. Operates reliably even with generator power.
Comprehensive Safety Protections:
Rapid shutdown and warnings for over-voltage, over-current, or high-voltage short circuits.
Warnings for sensor failure or disconnection.
Built-in temperature-limiting relay in the heating furnace; stops heating above 120°C.
Flexible Parameter Settings: Easily adjustable test temperature (0–125°C), AC voltage (500–2200V RMS), and DC voltage (0–500V).
User-Friendly Interface: Clear LCD display with intuitive Chinese menu prompts guides users through automated testing, storage, and printing.
Integrated Real-Time Clock: Automatically saves, displays, and prints test dates/times with results.
Test Cell Calibration: Enables assessment of cell cleanliness and assembly via electrode capacitance and tan δ measurement. Calibration data is stored for accurate calculation of relative permittivity and DC resistivity.
III. Technical Specifications
| Parameter | Specification |
|---|---|
| Power Supply | AC 220V ±10%, 50Hz/60Hz ±1% |
| Power Consumption | 100W |
| Dimensions (WxDxH) | 500 mm x 360 mm x 420 mm |
| Weight | 22 kg |
| Test Temperature | Range: 0°C to 125°C Accuracy: ±0.5°C |
| Test Voltages | AC (RMS): 500V to 2200V, Continuously adjustable, 50Hz DC: 0V to 500V, Continuously adjustable |
| Measurement Ranges | |
| Capacitance (Cx) | 5 pF to 200 pF |
| Relative Permittivity (εᵣ) | 1.000 to 30.000 |
| Dielectric Loss Factor (tan δ) | 0.00001 to 100 |
| DC Resistivity (ρ) | 2.5 MΩ·m to 20 TΩ·m |
| Measurement Accuracy | |
| Capacitance (Cx) | ±(1% of reading + 0.5 pF) |
| Relative Permittivity (εᵣ) | ±1% of reading |
| Dielectric Loss Factor (tan δ) | ±(1% of reading + 0.0001) |
| DC Resistivity (ρ) | ±10% of reading |
| Resolution | |
| Capacitance (Cx) | 0.01 pF |
| Relative Permittivity (εᵣ) | 0.001 |
| Dielectric Loss Factor (tan δ) | 0.00001 |
Products Cases

Company Profile

Certification

Related Products
Hot Tags: hzjd-2 transformer oil tan delta and resistivity tester, China hzjd-2 transformer oil tan delta and resistivity tester manufacturers, suppliers, factory, insulating oil power factor tester, Oil Tan Delta Tester, Oil Dielectric Loss And Resistivity Tester, oil tan delta and resistivity tester, dielectric oil power factor tester
Send Inquiry