200kVA/50kV Induction Series AC Resonance Test System
HZXB(L)-200kVA/50kV Induction Series AC Resonance Test System I. Testing object AC withstand voltage test of 22kV/600MW thermal power generator, capacity ≤0.2158uF, test frequency 50Hz, test voltage 47kV, test time 1min II. Main technical parameters and functions Rated capacity:200kVA; Rated...
200kVA/50kV Induction Series AC Resonance Test System
I.Testing object
AC resonance withstand voltage test of 22kV/600MW thermal power generator, capacity ≤0.2158uF, test frequency 50Hz, test voltage 47kV, test time 1min
II.Main technical parameters and functions
Rated capacity:200kVA;
Rated voltage:50kV;
Rated current:4A;
Operating frequency:power frequency 50Hz;
Output voltage waveform distortion rate:≤0.5%;
Allow continuous working hours:5min(under rated load);
Temperature rise after continuous operation for 5min under rated load: ≤65K;
Device's own quality factor:Q≥10;
System measuring accuracy:virtual value 1.5 class;
Output power:single 220V,50Hz;
Over current, over pressure and flashover protection are provided for the testing object;
Operating Temperature: –10 to +50 °C
Relative humidity:≤90%RH,Altitude≤1000m;
System configuration and parameters
Excitation transformer JLB-20kVA/5kV/0.4kV 1 set
Rated capacity:20kVA;
Input power:220V,single phase;
Output voltage:3kV
Type:Dry type
Weight: about 125kg;
Temperature rise of coil to air after
1 min rated operation:≤65K;
Operating bench HZXB-(L)-20kVA/380V (Including voltage regulator) 1 Set
Rated capacity:20kVA;
Input voltage:380V
Output voltage:0~250V;
Protection function: zero, overcurrent, overvoltage and flashover protection;
Weight:about 100kg;
Adjustable reactor DK(L-200kVA/50kV 1 Set

Rated capacity:200KVA;
Rated voltage:50kV;
Rated current:4A;
Adjustable inductance:47H~127H;
quality factor:Q≥10;
Type: Dry type, adjustable with iron core:;
Quantity:1 set;
Weight:about 180Kg ;
High voltage divider FRC-50kV 1 Set
Rated voltage:50kV
Testing accuracy:AC RMS 1.5 class;
Dielectric loss:tgσ≤0.5%;
The ratio of divided voltage:1000:1,accuracy:≤1.0%;
Weight:about 10Kg;
Compensating capacitor BC-50kV/0.08uF 1 Set
Rated voltage:50kV;
High voltage capacity:0.08uF
Weight:15kg
VI. System equipments List
List of equipment configuration
|
No. |
Name |
Model |
Unit |
quantity |
Comment |
|
1 |
Excitation transformer |
JLB-20kVA/5kV/0.4kV |
set |
1 |
|
|
2 |
Control Bench |
HZXB-(L)-20kVA/380V |
set |
1 |
|
|
3 |
Adjustable reactor |
DK-(L)-200kVA/50kV |
set |
1 |
|
|
4 |
Divider |
FRC-50kV |
set |
1 |
|
|
5 |
compensating capacitor |
BC-50kV/0.08uF |
set |
1 |
|
|
6 |
Testing Line |
set |
1 |
FAQ
1. When can I get a price quote?
You can contact us online or submit an inquiry. We typically provide a quote within 24 hours after receiving your request.
2. How do you handle after-sale service for overseas customers?
For issues occurring with our products, we offer:
12-month warranty coverage (see details below).
Online technical guidance to troubleshoot problems remotely.
Replacement parts shipped promptly based on your needs.
On-site support (if required): Our engineers can travel abroad to resolve critical issues.
3. What is the warranty period?
Our standard warranty period is 12 months (1 year). During this time, we provide:
Free technical support.
Replacement parts for manufacturing defects.
Solutions tailored to your specific issue.
Products Cases

Company Profile

Certification

Related Products

Hot Tags: 200kva/50kv induction series ac resonance test system, China 200kva/50kv induction series ac resonance test system manufacturers, suppliers, factory, variable frequency resonant test set, cables ac resonant test system, variable frequency ac series resonant test system, resonant voltage tester, AC Resonance Test System, series resonance voltage withstand test device