HZJB-D Single Phase Relay Protection Tester 0-150A Features 1.Output a full isolation way for adjustable DC voltage, Automatic protection for short circuit, overload and out range. 2.Maximum Output Current:0~150A. 3.Equipped with LCD digital AC/DC volt-ampere meter, can show the AC and DC...

 

HZJB-D Single Phase Relay Protection Tester 0-150A

 

 

Products Description

 

Features

Output Isolation and Protection: Outputs fully isolated adjustable DC voltage with automatic protection against short circuit, overload, and out-of-range conditions.

Maximum Output Current: 0–150 A.

Integrated Display: Equipped with an LCD digital AC/DC volt-ampere meter that displays AC and DC voltage and current values, stopwatch readings, potential, and contact status.

Internal Stopwatch and Contacts: Features an internal electric stopwatch with available electrical contacts (maximum potential 250 V). Supports dual-channel measurement.

Compact and Portable: Lightweight design, small volume, yet fully functional.

 

Technical Parameter

AC Output

Range(A)

No-load Voltage

(Minimum)V

Full-load Voltage

(Minimum)V

Full-load Current

(Maximum)A

0~10

90

80

10

0~40

25

22

40

0~100

10

<8

150

Range(V)

No-load Voltage

(Minimum)V

Full-load Voltage

(Minimum)V

Full-load Current

(Maximum)A

0~250(AC)

250

240

3

0~300(DC)

320

250

3

DC auxiliary Output

Range V

Voltage V

Maximum current A

0~110

120

0.5

110~220

220

0.5

 

Panel And Function Instruction

product-1306-1046

1.Stopwatch input terminal and stopwatch operation button:

Stopwatch input terminal: The Red terminal is START, The green terminal is STOP, The Black terminal is COM.

The buttons show "Reset", "Single / Dual", Press and hold more than 3 seconds shows (External start or external start, Default is external start), "(ON) Electric potential /Contact", "(OFF) Electric potential /Contact";

"Reset" for time reset, check if the stopwatch reset to zero before counting each time;

"Single / Dual Channel" for choosing stopwatch status (On default external dual channel), Press and hold more than 3 seconds could choose external start or internal start. Internal start means synchronization start, contacts or potential stop when internal output or removal. External single channel means OFF terminal contact or potential start/end, External dual channel means ON terminal contact or potential start/end.

"(ON) Electric potential /Contact" use for Electric potential on or Contact on.

"(OFF) Electric potential /Contact" use for Electric potential off or Contact off.

2.LCD can display the measured output voltage and current, action time and contact or potential state;

Line 1: Select Grade display output voltage and current value;

Line 2: Stopwatch measured value Select Grade display output voltage and current value; Stopwatch measure value display on the left, current status of stopwatch input terminal display on the right;

Line 3: Left:Display external start or internal start, Right: And the table state;

Line 4: Left:Display the current states are single or dual , Right: The stopwatch state.

3.Resistors and Capacitors:

(1)Resistance: 0.5Ω·10A,1Ω·5A,25Ω·2A,100Ω·0.7A,500Ω·0.3A,1000Ω·0.22A,2500Ω·0.14A; Obtain the resistance by select different terminal; accurately adjust the required value of voltage and current by string into the voltage and current output grade;

(2)Capacitor: 10uF/AC450V.

4.Measure selection indicate: 0~100A,0~40A,0~10A,0~250V,0~300V,external input; Led Indicator Lights Up shows output value in LCD.

5.Split/join the auxiliary contact; the contact synchronize with 10 point "ON/ OFF" button.

6.AC voltage and current output terminal: 0~10A·90V,0~40A·25V,0~100A·10V,0~250V·3A,The black terminal is COM.

7.DC current output terminal: 0~300V·3A,the terminal is independent output Red + Black -.

8.External input VOLTMETER & AMMETER; display measure value by select external input grade of "Output selection"button.

9.Current and voltage output Knob: Adjust output value by match "ON/ OFF" of 10 contact button.

10."Output Selection" and "ON/ OFF" button: "Output Selection" button is only used in the removal state match measure selection indication; "ON/ OFF" button is used for controlling output and removal, Top left LED light up when output, lights out when removal.

11.Auxiliary DC voltage power: can finely adjust voltage value independently, Select grade 0~110V/ 110~220V by control "ON/ OFF" button.

12.Computer interface: for debugging device, downloading programs and updating software.

13.Power switch: Device power switch.

14.Power outlet.

15.Grounding terminal.

16.Contrast adjustment: adjust the brightness of LCD.

 

Caution

Grounding: The device must be reliably grounded during operation to ensure safety.

Display Adjustment: If the display appears too dark or completely black, adjust the "Contrast Adjustment" control to achieve optimal visibility.

Measurement Selection: The measurement selection button is disabled once current output begins. Ensure all measurement parameters are selected before initiating current output.

 

Packing List

No.

Item

Qty

1

Main engine

1

2

Power line

1

3

Test lead package

1

4

test lead(2.5mm2-2.5m)

2

5

test lead(2.5mm2-0.5m)

2

6

test lead((8mm2-2m)

2

7

test lead(1.2mm2-2.5m)

3

8

Double core sheathed wire(2×1.2mm2-2.5m)

1

9

Transparent ground wire(2.5mm2-2m)

1

10

Insert(6mm)

4

11

Dedicated clip

12

12

Transition post

4

13

Pin plug

4

14

Fuse tube

4

 

 

FAQ

 

1. When can I get a price quote?

You can contact us online or submit an inquiry. We typically provide a quote within 24 hours after receiving your request.

 

2. How do you handle after-sale service for overseas customers?

For issues occurring with our products, we offer:

12-month warranty coverage (see details below).

Online technical guidance to troubleshoot problems remotely.

Replacement parts shipped promptly based on your needs.

On-site support (if required): Our engineers can travel abroad to resolve critical issues.

IMG20241121162722

3. What is the warranty period?

Our standard warranty period is 12 months (1 year). During this time, we provide:

Free technical support.

Replacement parts for manufacturing defects.

Solutions tailored to your specific issue.

 

Products Cases

 

HZ-20A04

 

Company Profile

 

af7e9172c2e3db1e6c4b786d81dd1ea7

 

Certification

 

Manufacturing-Price-Portable-Automatic-Current-Transformer-CT-PT-Testing-System 1

 

 

Related Products

 

 

product-750-1077

 

 

 

 

 

 

 

Hot Tags: hzjb-d single phase relay protection tester 0-150a, China hzjb-d single phase relay protection tester 0-150a manufacturers, suppliers, factory, Three Phase Relay Protection Tester, secondary relay tester, Six Phase Relay Test Set, Relay Protection Tester, Relay Protection Test Set, Relay Protection Test Equipment

Send Inquiry

(0/10)

clearall