12kV Capacitance And Dissipation Factor Test Set
12kV Capacitance and Dissipation Factor Test Set Dielectric loss measurement is a very basic method in insulation test, which can effectively find out the whole damp deterioration and local defects of insulation of electrical equipment. It is widely used in electrical manufacturing, electrical...
12kV Capacitance and Dissipation Factor Test Set
Product Description



The measurement of dielectric loss of transformer, mutual inductor, reactor, capacitor, bushing and lightning arrester is the most basic method to measure its insulation performance. The dielectric loss tester has broken through the traditional bridge measurement method, adopting frequency conversion power supply technology, using single chip microcomputer and modern electronic technology to carry out automatic frequency conversion, mode/number conversion and data operation. Strong anti-interference ability, fast test speed, high precision, automatic digitization, easy operation; Power supply adopts high-power switching power supply, output 45Hz and 55Hz pure sinusoidal wave, automatically pressurize, can provide up to 10 kv voltage; Automatic filter 50Hz interference, suitable for substation and other electromagnetic interference large field test. Widely used in the power industry transformer, mutual inductor , casing, capacitor, lightning arrester and other equipment dielectric loss measurement.
Tech Data
| Item | Specification |
| Accuracy | Cx: ±(readings×1%+1 pF)tgδ: ±(readings×1%+0.00040) |
| Anti‑interference index | Frequency‑conversion anti‑interference; above‑mentioned accuracy can be maintained under 200% interference |
| Capacitance range | Internal high‑voltage: 3 pF~60000 pF/12 kV; 60 pF~1 μF/0.5 kVExternal high‑voltage: 3 pF~1.5 μF/12 kV; 60 pF~30 μF/0.5 kV |
| Resolution | Up to 0.001 pF, 4‑bit significant digits |
| Tgδ range | No limit; resolution: 0.001%. Automatic identification for capacitance, inductance and resistance |
| Test current range | 10 μA~5 A |
| Internal high‑voltage setting voltage range | 0.5~12 kV |
Discussion of Frequency Conversion Measurement
1,Frequency conversion measurement
When the interference is very serious, the frequency conversion measurement can get accurate and reliable results. For example, when measuring with 55Hz, the measuring system only allows 55Hz signal to pass, and 50Hz interference signal is effectively suppressed. The reason is that the measuring system can easily distinguish different frequencies. The following simple calculation can illustrate the effect of frequency selection measurement:
The sinusoidal waves with a difference of 1 times of the two frequencies are superimposed together, and the high-frequency ones are interference with a amplitude 10 times of the low-frequency ones:
Y=1.234sin(x+5.678°)+12.34sin(2x+87.65°)
At x=0/90/180/270°,four measurements are obtained
Y0=12.4517,Y1= -11.1017,Y2=12.2075,Y3= -13.5576,
Calculate A=Y1-Y3=2.4559,B=Y0-Y2=0.2442,then:
φ=tg-1(B/A)=5.678° V= A2+B2/2=1.234
This is just the phase and amplitude of the low frequency part, and the interference is suppressed. The measurement points of the actual waveform are up to tens of thousands, and the calculation is very large.
2,The relationship between frequency and dielectric loss
There are two ideal models of RC series and parallel dielectric losses:series model tgδ=2πfRC,Parallel model tgδ=1/(2πfRC),tgδis proportional and inverse with the frequency f.As shown in the figure, f has a great influence on the two models of perfect direct ratio and perfect inverse ratio. However, the actual capacitor is a hybrid model with many models interwoven, so the influence off is small.
FAQ
1. When can I get a price quote?
You can contact us online or submit an inquiry. We typically provide a quote within 24 hours after receiving your request.
2. How do you handle after-sale service for overseas customers?
For issues occurring with our products, we offer:
12-month warranty coverage (see details below).
Online technical guidance to troubleshoot problems remotely.
Replacement parts shipped promptly based on your needs.
On-site support (if required): Our engineers can travel abroad to resolve critical issues.
3. What is the warranty period?
Our standard warranty period is 12 months (1 year). During this time, we provide:
Free technical support.
Replacement parts for manufacturing defects.
Solutions tailored to your specific issue.