Online Dga Monitoring System For Dissolved Gas Content in Transformer Oil
HZGC-1210 Online Dga Monitoring System for Dissolved Gas Content in Transformer Oil Products Description HZGC-1210 On-line Oil Chromatography Monitoring System is capable of fully automated quantitative cycle cleaning, oil sampling, oil-gas separation, sample analysis, data processing, and real-time...
Online Dga Monitoring System for Dissolved Gas Content in Transformer Oil
Product Description
HZGC-1210 On-line Oil Chromatography Monitoring System is capable of fully automated quantitative cycle cleaning, oil sampling, oil-gas separation, sample analysis, data processing, and real-time alarms. It continuously monitors the content and growth rate of dissolved fault gases in the oil of oil-immersed high-voltage equipment such as transformers. Combined with an integrated fault diagnosis expert system, it predicts potential equipment hazards, thereby preventing accidents, reducing significant losses, and enhancing operational reliability.
Developed through decades of expertise in power chromatography and degassing technology, and refined with insights from domestic and international online monitoring solutions, the HZGC-1210 delivers outstanding stability, reliability, and precision.
Key Features
Comprehensive Detection:
Online monitoring of concentrations and growth rates of H₂, CO, CO₂, CH₄, C₂H₄, C₂H₂, C₂H₆, with optional measurement of H₂O, O₂, and N₂.
Reliable Sampling & Analysis:
Employs quantitative cleaning and cyclic sampling to accurately reflect dissolved gas states in transformer oil.
Safe Oil‑Gas Separation:
Pollution‑free process allows user‑selectable oil discharge options.
Advanced Separation & Detection:
Dedicated composite column improves component separation.
Imported Australian EIP detector enhances hydrocarbon detection sensitivity.
High Precision & Stability:
Gas detection error within ±10%, utilizing oversampling Δ‑∑ ADC technology with 24‑bit resolution and auto‑calibration.
Flexible Data Management:
Supports diverse display and query modes, report/tend generation, and 10‑year historical data storage.
Robust Communication:
Standard network protocols enable reliable remote data transmission and system control.
Wide Environmental Adaptability:
Proven performance in extreme cold, heat, humidity, and high‑altitude conditions.
Strong EMI Resistance:
Compliant with GB/T17626 and IEC61000 electromagnetic compatibility standards.
Intelligent Alarms:
Two‑level alarm function with remote alarm signaling.
Open Database Support:
Compatible with power system LAN integration.
|
No. |
Technical parameter name |
Value provided |
|
|
1 |
System model |
HZGC-1210 |
|
|
2 |
Working temperature |
-40℃~+65℃ |
|
|
3 |
Working environment humidity |
Relative humidity 5 to 95% (no condensation and ice inside the device) |
|
|
4 |
Atmospheric pressure |
70kPa~110kPa |
|
|
5 |
Working power |
AC 220 V±10%, 50/60Hz |
|
|
6 |
Monitoring component |
Seven gas components such as H2, CO, CO2, CH4, C2H4,C2H2,C2H6,H20(optional),O2(optional),N2(optional)and micro-water, relative growth rate and absolute growth rate; oil micro-water monitoring( optional) |
|
|
7 |
Analytical diagnostic function |
Analyze and diagnose monitoring data by improved three-ratio method, David triangle method and cube graph method, and provide original spectrum |
|
|
8 |
Minimum detection period |
60 minutes, user-settable, default as 24 hours |
|
|
9 |
Sampling method |
Cyclic sampling to safely and realistically reflect the true state of the gas in the transformer |
|
|
10 |
Oil and gas separation method |
Vacuum full degassing |
|
|
11 |
Data storage life |
≥ 10 years |
|
|
12 |
Equipped with carrier gas |
Gas source generator |
|
|
13 |
Monitoring gas |
Test scope |
Minimum detection |
|
1) |
H2 |
2~ 2000 µ l/l |
2µ l/l |
|
2) |
CO |
25~ 3000 µ l/l |
25 µ l/l |
|
3) |
CO2 |
25~ 15000 µ l/l |
25 µ l/l |
|
4) |
CH4 |
0.5~ 600 µ l/l |
0.5 µ l/l |
|
5) |
C2H4 |
0.5 ~ 600 µ l/l |
0.5 µ l/l |
|
6) |
C2H6 |
0.5~ 600 µ l/l |
0.5µ l/l |
|
7) |
C2H2 |
0.5~ 200 µ l/l |
0.5 µ l/l(0.2ul/lcustomization required) |
|
8) |
O2 |
500~ 100000µ l/l |
500µ l/l |
|
9) |
N2 |
500~ 50000µ l/l |
500µ l/l |
|
10) |
H2O(Optional) |
1 ~ 800 µ l/l |
|
|
11) |
Total hydrocarbon |
2~ 2000 µ l/l |
|
|
12) |
Total gas content (optional) |
0.2 ~ 15% |
|
|
13) |
Stability (measurement deviation) |
The deviation of the monitoring results of the same oil sample under the same test conditions does not exceed ± 5% (medium concentration) |
|
|
14) |
Electrostatic discharge immunity |
Level 4,± 8kV-± 15kV |
|
|
15) |
Electrical fast transient burst immunity |
Level 4,± 4kV |
|
|
16) |
Surge (impact) immunity |
Level 4,± 4kV |
|
|
17) |
Earthquake resistance: seismic waves are sine waves Duration: three cycles, safety factor 1.67 |
Earthquake intensity 9 degrees area: Ground horizontal acceleration 0.4g, ground vertical acceleration 0.2g |
|
|
Earthquake intensity 8 degrees: Ground horizontal acceleration 0.25g, ground vertical acceleration 0.125g |
|||
|
Earthquake intensity 7 degrees: Ground horizontal acceleration 0.2g, ground vertical acceleration 0.1g |
|||
|
18) |
Extreme ambient temperature for storage and transportation |
-40 ℃ ~+ 80 ℃ |
|
|
19) |
Protective performance of the outer casing |
Outdoor mounting components (this system and communication control unit) IP56 |
|
|
20) |
Dimensions |
Width 600mm × depth 535mm × height 1200mm |
|
|
21) |
Total Weight |
160kg |
|
|
22) |
Basic size |
Length 600mm × width 500mm × ground height around 200mm Detailed construction see pedestal construction drawing |
|
FAQ
1. When can I get a price quote?
You can contact us online or submit an inquiry. We typically provide a quote within 24 hours after receiving your request.
2. How do you handle after-sale service for overseas customers?
For issues occurring with our products, we offer:
12-month warranty coverage (see details below).
Online technical guidance to troubleshoot problems remotely.
Replacement parts shipped promptly based on your needs.
On-site support (if required): Our engineers can travel abroad to resolve critical issues.
3. What is the warranty period?
Our standard warranty period is 12 months (1 year). During this time, we provide:
Free technical support.
Replacement parts for manufacturing defects.
Solutions tailored to your specific issue.
Products Cases

Company Profile

Certification

Related Products
Hot Tags: online dga monitoring system for dissolved gas content in transformer oil, China online dga monitoring system for dissolved gas content in transformer oil manufacturers, suppliers, factory, clamp earth tester, contact angle measurement equipment, Energy Meter Calibrator, ct pt tester, different other products, hand held power quality analyser