400kV 20kJ Lightning Impulse Voltage Generator

400kV 20kJ Lightning Impulse Voltage Generator

400kV 20kJ Lightning Impulse Voltage Generator Products Description I. Scope of Application This impulse voltage generator is designed for standard lightning impulse (1.2/50μs) full-wave testing of: Air gaps Reactor switches Insulator strings Bushings Power transformers (including 35kV and...

400kV 20kJ Lightning Impulse Voltage Generator

 

Product introduction

 

400kV 20kJ Lightning Impulse Voltage Generator is a high-voltage testing device used to generate a maximum voltage of 400kV and store 20kJ of energy to simulate lightning impulse waves in laboratory conditions.

 

Impulse Voltage Test System 1

Impulse Voltage Test System 2

Impulse Voltage Test System 3

Impulse Voltage Test System 4

Impulse Voltage Test System 5

 

Operating Conditions

 

Altitude: ≤1,000 m

Ambient Temperature: -25℃ to +45℃

Relative Humidity: ≤90% (at 20℃)

Max Daily Temperature Variation: ≤25℃

Installation: Indoor only

Environmental Requirements:

No conductive dust

No fire/explosion hazards

No corrosive gases affecting metals or insulation

Power Supply:

Sine waveform with <5% total harmonic distortion

 

Technical Specifications

 

Parameter Value/Description
1. Nominal Voltage 400kV
2. Rated Voltage 100kV
3. Nominal Energy 20kJ
4. Total Impulse Capacitance 0.25μF (8 × 2μF/50kV capacitors in parallel)
5. Number of Stages 4
6. Standard Waveform 1.2/50μs lightning impulse
- Voltage Utilization >85% (≥90% under no-load 400pF condition)
- Compliance Meets GB311 & GB16927 national standards
7. Minimum Output Voltage ≥10% of nominal voltage
8. Duty Cycle - ≥70% rated voltage: 120s interval between discharges
  - <70% rated voltage: 60s interval between discharges

 

FAQ

 

Q: What high-voltage switch technology is used in the generator to ensure synchronization?

A: We use high-performance SF6 gas three-electrode trigger switches to ensure synchronization with a deviation of less than 100 ns for all discharge levels.

Q: What is the partial discharge (PD) level of the generator?

A: The partial discharge (PD) level is strictly controlled to < 5 pC at rated voltage, ensuring long-term insulation reliability.

Q: What are the steps in the customization process?

A: Requirement confirmation -> Technical solution design -> Customer review -> Contract signing -> Manufacturing -> Factory inspection -> Delivery and installation.

Q: What is the typical production cycle for customized products?

A: The standard production cycle for customized products is typically 8 to 12 weeks, with specific timing as per the contract agreement.

Q: What type of packaging is used to ensure safe transportation?

A: We use sturdy wooden crates (fumigated treatment) and moisture-proof, shock-absorbing inner linings for multi-layer packaging, ensuring the equipment is not damaged during sea or air transport.


IMG20241121162722

 

Product Cases

 

HZ-20A04

 

Company Profile

 

af7e9172c2e3db1e6c4b786d81dd1ea7

 

certification

 

Our company has obtained utility model patents, ISO 9001, CE, TÜV, and other certifications, ensuring that the products meet international quality standards.

 

Manufacturing-Price-Portable-Automatic-Current-Transformer-CT-PT-Testing-System 1

 

Related Products

 

product-750-1077

 

Hot Tags: 400kV 20kJ Lightning Impulse Voltage Generator, China 400kV 20kJ Lightning Impulse Voltage Generator manufacturers, suppliers, factory, Lightning Impulse Voltage Generator, 400kV Impulse Voltage Generator, impulse high voltage generator, lighting impulse voltage equipment, impulse voltage generator

Send Inquiry

(0/10)

clearall