The SF6 Gas Testing Transformer features an advanced design and robust construction. Its compact and lightweight design makes it easy to transport and set up in various field conditions. With high voltage output capability, this transformer enables precise testing of SF6 gas pressure, ensuring that your equipment operates within the required parameters.

Sf6 Inflatable Testing Transformer

Products Description

 

The SF6 Inflatable Testing Transformer is a high-voltage test transformer with SF6 gas insulation, suitable for withstand voltage testing of substations, switchgear, and high-voltage electrical appliances.

 

Sf6 Inflatable Testing Transformer Technical Parameters

 

1.Technical parameters of HZQ series alternating current test transformers

Model

Capacity(KVA)

High Frequency Voltage

Output Voltage

(KV)

High Frequency

Voltage

Output

Current(mA)

Low Frequency Voltage input

Ratio

Tempera- ture(℃)

raised/

30 minute

AC

DC

AC

DC

V

A

HZQ -30

30

150

210

200

100

380

75

1500

10

Note: 100KVA and the above input voltage may enhance to 3000V or proposed by the users.

 

HZXC HV Hipot Control Unit (≤10KVA) Of Sf6 Inflatable Testing Transformer

 

Control Box(10KVA)

If the capacity of main control box is not more than10KVA the panel of the main control box is as figure 4.

product-1267-956

Figure 4 Panel of main control box

 

The operation of the insulation test with HZJ series HIPOT tester is as follow:

 

Connect the grounding cables for the test object, high-voltage transformer, and main control box.

If the test object is capacitive, fully discharge it before testing.

Connect the tester to the test object according to Figure 3.

Power on the main control box.

Confirm the required withstand voltage value.

Set the over-current protection value using the pointer on the over-current relay panel.

Set the voltage regulator to the zero position, then press the Close button on the control panel to enable the high-voltage output unit.
If the regulator is not at zero, the high-voltage output unit cannot be enabled. The zero-position indicator on the panel will confirm correct status.

Slowly increase the output voltage to the specified test value while monitoring the high-voltage and low-voltage current meters.

Start the timer using the timer switch on the main control box once the test voltage is applied.

If the output current exceeds the preset value, the over-current protection will immediately cut off the power to the high-voltage transformer, and the test will be deemed failed.

When the timer reaches the preset time, an audible alarm will sound. If no over-current trip occurs before the alarm, the test is considered passed.

Press the Open button to disconnect the power supply to the high-voltage transformer after the test.

Fully discharge the high-voltage circuit of the test object before disconnecting any cables.

 

Please do not start the test if any part of the tester is damaged.

Products Cases

 

HZ-20A04

 

Company Profile

 

af7e9172c2e3db1e6c4b786d81dd1ea7

 

Certifaction

 

Manufacturing-Price-Portable-Automatic-Current-Transformer-CT-PT-Testing-System 1

 

 

Related Products

 

 

image013001

 

Hot Tags: sf6 inflatable testing transformer, China sf6 inflatable testing transformer manufacturers, suppliers, factory, dry type testing transformer, power frequency test transformer, 100 kv hipot tester, ac dc withstand voltage tester, sf6 inflatable testing transformer, ac dc high voltage testing transformer

Send Inquiry

(0/10)

clearall