3000A Primary Current Injection Test Equipment

3000A Primary Current Injection Test Equipment

3000A Primary Current Injection Test Equipment Products Description I. Product Overview The HZ5373 3000A Primary Current Injection Test Equipment is our proprietary test equipment. Integrating domestic and international technological advantages, it employs CNC technology for enhanced...

3000A Primary Current Injection Test Equipment

 

Product Description

 

I. Product Overview

The HZ5373 3000A Primary Current Injection Test Equipment is our proprietary test equipment. Integrating domestic and international technological advantages, it employs CNC technology for enhanced anti-interference capability. Compared to previous generations, its adoption of low-power, high-capacity autotransformers and high-permeability iron-core converters enables superior power density, compact size, and reduced weight.
Primary Applications:

Primary busbar protection testing

Current transformer (CT) ratio verification
Industries Served: Power utilities, railways, petrochemical, metallurgy, mining, R&D, and electrical testing sites.

 

II. Technical Specifications

1. Key Parameters

Item Specification
Model HZ5373 3000A High-Current Generator
Environmental Class Category III per GB6587.1-86 (suitable for outdoor use)
Input Voltage AC380V ±10%
Rated Power 30 kVA
Output Current AC 0–3000A (steplessly adjustable)
• Digitally displayed on panel
Output Voltage >10 V
Output Waveform Standard sine wave
• Ripple coefficient <0.3%
• Exceeds power system standards
Measurement Accuracy 0.3% (using 0.2S-class materials)
• Continuous smooth adjustment
• True RMS current/voltage display
Current Stability 0.2%
Protections Overcurrent, Overvoltage
Wiring Method Customizable per requirements

 

2. Operating Guidelines

Pre-Test Check

Verify wiring correctness and connection integrity.

Abnormal Conditions

Immediately power off if sparking, smoke, or startup failure occurs. Recheck wiring.

Output Terminal Requirement

Output terminals must form a closed loop; otherwise, no current will be generated.

Output Cables

Included: 2×3m test cables (standard).

External copper wire selection: ≥10 A/mm² cross-section.

Operating Duration

Design Capacity: 5 minutes (short-term duty).

Batch Testing: Limit to ≤2.5 minutes per operation.

Extended Tests (e.g., 30-min to 24-hr temperature rise): Use long-term thermal design parameters.

 

 