DC Withstand Voltage Tester Operation Steps

May 03, 2024

1. The integrity of the DC withstand voltage test device should be checked before use. The connecting cables should not be broken or short-circuited, and the equipment should not be damaged such as cracks.
2. Place the chassis and voltage multiplier in a suitable position and connect the cable, grounding wire and power line respectively. The protective grounding wire, working grounding wire and grounding wire of the discharge rod should be connected to the ground wire of the test piece separately (i.e., one-point grounding). It is strictly forbidden to connect the grounding wires in series. For this purpose, the ZGF special grounding wire should be used.
3. Put the power switch in the off position and check that the voltage regulating potentiometer should be at zero position. The overvoltage protection setting value is generally 1.1 times the test voltage.
4. No-load boost detection overvoltage protection setting is sensitive.
5. Turn on the power switch, and the green light is on, indicating that the power is on.
6. Press the red button, and the red light is on, indicating that the high voltage is on.
7. Slowly adjust the voltage regulating potentiometer in clockwise direction, and the output end will start to increase the voltage from zero. After the voltage reaches the required voltage, record the ammeter reading at the specified time, and check whether there are any abnormal phenomena and sounds in the control box and high-voltage output line.
8. Reduce the voltage. After returning the voltage regulating potentiometer to zero, press the green button immediately to cut off the high voltage and turn off the power switch.
9. Perform leakage and DC withstand voltage tests on the test product. After the inspection test confirms that there are no abnormalities in the tester, the leakage and DC withstand voltage tests of the test product can be started. Connect the test product, ground wire, etc., and turn on the power after checking that they are correct.
10. Boost to the required voltage or current. The boost speed is preferably a test voltage of 35KV per second. For large-capacitance test products, it is also necessary to monitor the charging current of the ammeter to ensure that it does not exceed the maximum charging current of the tester. For small capacitance test products such as zinc oxide lightning arresters and magnetic blow arresters, first increase the voltage (power supply) to 95%, then slowly and carefully increase it to the required voltage (current), and then read the voltage (current) value from the digital display. If you need to measure 0.75UDC1mA for zinc oxide lightning arresters, first increase it to UDC~1mA voltage value, then press the yellow button, then the voltage will drop to 75% of the original and keep this state. At this time, the microampere number can be read. After the measurement is completed, the voltage potentiometer returns to zero counterclockwise and presses the green button. Press the red button when you need to increase the voltage again.
If necessary, use an external high-voltage voltage divider to compare the DC high voltage indication on the control box.
11. After the test is completed, reduce the voltage and turn off the power.