HV Vacuum Switch Interrupter Vacuity Tester
Huazheng HZ-KG7 HV Vacuum Switch Interrupter Vacuity Tester Products Description The HZ-KG7 represents our latest generation vacuum switchgear tester, evolving from the HZ-KG6 based on extensive field user feedback. It delivers higher accuracy, superior stability, and increased capacity for assessing vacuum...
HV Vacuum Switch Interrupter Vacuity Tester
Products Description
The HZ-KG7 represents our latest generation vacuum switchgear tester, evolved from the HZ-KG6 based on extensive field user feedback. It delivers higher accuracy, superior stability, and increased capacity for assessing vacuum integrity.
Overcoming Traditional Limitations
Conventional frequency withstand voltage testing only identifies severely degraded vacuum interrupters (VIs). Crucially, VIs can fail at vacuum levels between 10⁻² to 10⁻¹ Pa, even when breakdown voltage remains within normal ranges.
Innovative Non-Destructive Testing
The HZ-KG7 eliminates the need for disassembly. Utilizing novel excitation coils and the magnetron discharge method, it directly measures the vacuum level within the interrupter chamber. Computerized synchronous control, data acquisition, and processing ensure a remarkable field-test sensitivity of 10⁻⁵ Pa.
Key Features & Benefits:
Non-Destructive Measurement: Tests vacuum integrity without disassembling the switchgear.
High Sensitivity & Accuracy: Detects vacuum levels down to 10⁻⁵ Pa with defined precision.
Advanced Technology: Proprietary excitation coils and data processing algorithms.
User-Friendly: Practical, easy to operate design.
Versatile Application: Widely used in power, steel, petrochemical, textile, coal, railway, and other industries employing vacuum switches.
Specifications
Detection Object: Various models of vacuum circuit breakers/switches.
Detection Method: Non-destructive measurement using novel excitation coils (magnetron discharge).
Application: Universal instrument for measuring vacuum levels in diverse open-magnetic-field vacuum interrupters.
Detection Range: 10⁻⁵ Pa to 10⁻¹ Pa.
Measurement Accuracy:
10⁻⁵ Pa to 10⁻⁴ Pa: ±15%
10⁻⁴ Pa to 10⁻³ Pa: ±15%
10⁻³ Pa to 10⁻² Pa: ±10%
10⁻² Pa to 10⁻¹ Pa: ±10%
Excitation Voltage: 1700 V.
Pulsed High Voltage: 30 kV.
Contact Gap During Test: Normal operating open distance.
Operating Environment: -20°C to +40°C.
Weight: 24 kg.
Dimensions (L x W x H): 420 mm x 320 mm x 280 mm.
Sensing Method: Magnetic coil.
Testing Principle
Setup: The VI's contact poles are separated to their normal operating distance. High-voltage pulses are applied across the contacts. The VI is placed within a spiral coil or has dedicated electromagnetic coils positioned externally.
Field Generation: This configuration generates a synchronized high-voltage pulsed magnetic field within the interrupter chamber.
Ionization: Under the combined influence of the strong electric field and pulsed magnetic field, electrons inside the chamber follow spiral paths. These electrons collide with residual gas molecules, causing ionization.
Ion Current: The resulting ion current is directly proportional to the density of the residual gas – that is, the vacuum level (pressure).
Calibration & Measurement: For specific VI types (due to structural differences), calibration curves establish the precise relationship between the measured ion current and the actual vacuum level at defined contact gaps and field strengths. By detecting the ion current produced during the test and referencing the pre-calibrated curve for that VI type, the instrument accurately determines the vacuum pressure inside the chamber.
FAQ
1. When can I get a price quote?
You can contact us online or submit an inquiry. We typically provide a quote within 24 hours after receiving your request.
2. How do you handle after-sale service for overseas customers?
For issues occurring with our products, we offer:
12-month warranty coverage (see details below).
Online technical guidance to troubleshoot problems remotely.
Replacement parts shipped promptly based on your needs.
On-site support (if required): Our engineers can travel abroad to resolve critical issues.
3. What is the warranty period?
Our standard warranty period is 12 months (1 year). During this time, we provide:
Free technical support.
Replacement parts for manufacturing defects.
Solutions tailored to your specific issue.
Products Cases

Company Profile

Certification

Related Products
Hot Tags: hv vacuum switch interrupter vacuity tester, China hv vacuum switch interrupter vacuity tester manufacturers, suppliers, factory, vaccum circuit breaker analyzer, vaccum cb test, Switch Interrupter Vacuity Tester
Send Inquiry